go-v.orgdoi

Measurements and Simulation of Supraharmonic Resonances in Public Low Voltage Networks

M. Klatt, Kaiser, Franziska, Jan Meyer, Christian Lakenbrink, Christoph Gaßner · CIRED · 2019

  • DOI 10.34890/455
  • Publisher CIRED
  • Type article
  • Issued 2019

Not cached yet. This record was fetched live for this request and is stored after the lookup. Reopening the page should serve the cached copy.

CIRED · CIRED · article · 2019

Abstract

Voltages and currents in the frequency range from 2 to 150 kHz (supraharmonics) are generally assumed to have a short distance of propagation. They are expected to be damped within the direct neighborhood and have their highest magnitude directly at their source. This paper presents measurements of the supraharmonic propagation in a typical residential and a typical commercial low voltage network. While an effective damping is observed in upstream direction, in downstream direction significant resonance amplification at frequencies between 2 and 20 kHz was found. For one network, the resonance is validated by simulation. The results show a good match with the measured values.

Open the resolved locator · 10.34890/455

Metadata licence: OpenAlex metadata (CC0)

Registry
OpenAlex DOI index + API
Fetched
2026-11-20 02:22 UTC
Cache state
not cached yet (bulk-index+openalex)
Locator
https://doi.org/10.34890/455
Metadata licence
OpenAlex metadata (CC0)
Scope
Metadata as returned by the resolver; abstracts are never generated here.