Evaluation of different local var control strategies in low voltage grids
Daniel-Leon Schultis, Albana Ilo, Christian Schirmer · CIRED · 2018
Not cached yet. This record was fetched live for this request and is stored after the lookup. Reopening the page should serve the cached copy.
CIRED · CIRED · article · 2018
Abstract
This paper compares for the first time the impact of different var-control strategies on the behaviour of low voltage grids. Besides existing control strategies like Q(U)- and cosφ(P)-control of PV-inverters also the new ones, namely L(U)-control with or without Q-Autarkic customers, are investigated. The assessment of different control strategies is made by means of social and technical criteria. Investigations show that involving the prosumer-owned inverters in voltage control entails in principle social issues like discrimination and threat to data privacy.
Local cosφ(P)- and Q(U)-control cause relatively high grid losses, extensive Q-exchanges between medium and low voltage grids and thus also considerable distribution transformer loadings. The application of L(U)-control mitigates the social issues and fulfils best the technical criteria. In this case the network operator is able to perform an effective voltage control by using his own devices. This control strategy enables the prosumers to internally compensate their reactive power needs; thus acting Q-Autarkic.
Open the resolved locator · 10.34890/173
Metadata licence: OpenAlex metadata (CC0)