The measured energy impact of air leakage on frame wall systems
S. Bhattacharyya · OSTI OAI (U.S. Department of Energy Office of Scientific and Technical Information) · 1991
Not cached yet. This record was fetched live for this request and is stored after the lookup. Reopening the page should serve the cached copy.
OSTI OAI (U.S. Department of Energy Office of Scientific and Technical Information) · Office of Scientific and Technical Information · report · 1991
Abstract
Infiltration is customarily assumed to increase the heating and cooling load of a building by an amount equal to the mass flow rate of the infiltration times the enthalpy difference between the inside and outside air -- with the latent portion of the enthalpy difference sometimes neglected. An experimental and analytical investigation has been conducted on the actual energy impact of air leakage on frame wall systems.
Calorimetric measurements conducted on a small test cell and on a well characterized stud-cavity wall specimen with measured amounts of air leakage introduced under a variety of controlled conditions and configurations show convincingly that infiltration can lead to a much smaller change in the energy load than is customarily calculated. The data also suggest that the phenomenon occurs in full-sized houses as well. Infiltration Heat Exchange Effectiveness (IHEE),{var epsilon}, is introduced as a measure of the effectiveness of a building in recovering'' heat otherwise lost (or gained) because of infiltration.
Measurements show that {var epsilon} increases as: (a) flow rate decreases; (b) flow path length increases; and, (c) hole/crack size decreases.