Report on sampling and analysis of exhaust air at the 221-T and 2706-T buildings
Westinghouse Hanford Co., Richland, WA (United States), M STAUFFER, USDOE Office of Environmental Restoration and Waste Management, Washington, DC (United States) · OSTI OAI (U.S. Department of Energy Office of Scientific and Technical Information) · 1997
Not cached yet. This record was fetched live for this request and is stored after the lookup. Reopening the page should serve the cached copy.
OSTI OAI (U.S. Department of Energy Office of Scientific and Technical Information) · Office of Scientific and Technical Information · report · 1997
Abstract
This report presents analytical results from exhaust air samples collected at stacks 221-T and 2706-T of the T-Plant. The samples were collected with SUMMA canisters over a 24 hour interval and were analyzed by gas chromatography-mass spectrometry using a modified EPA TO-14 procedure. The data suggest that the buildings had generally low concentrations of volatile organic compounds (< 40 ppbv). However, samples from building 2706-T did have significant amounts of non-target higher-boiling hydrocarbons, probably from a petroleum destination fraction.
Open the resolved locator · 10.2172/313367
Metadata licence: OpenAlex metadata (CC0)